Anthropic 2028年算力能源结构:87%天然气11%煤电

87% of the Anthropic power will come from gas and 11% from coal in 2028

原文
发到 X
推荐理由

深度拆解 AI 巨头背后的能源账本,用数据揭示算力扩张带来的巨大碳足迹与环境代价,对关注 AI 基础设施可持续性的从业者极具参考价值。

In The AI Gas Rush: Risks and Implications of “Bring Your Own Power”, we dug into how data centers are increasingly securing their own dedicated primary power generation rather than relying solely on utilities to procure power (“BYOP”). We identified 177 GW of planned BYOP gas capacity—enough to power 65% of all US homes. Conversely, we found renewables are much less common than gas for BYOP: we estimate that for current proposals, less than 20% of energy generation will come from renewable sources by 2032.

在《AI燃气热潮:“自带电源”的风险与影响》一文中,我们深入探讨了数据中心如何越来越多地自行 securing 专用的一次性发电能力,而不是完全依赖公用事业公司来采购电力(“BYOP”)。我们确定了177 GW的计划中BYOP燃气容量——足以供应美国65%的家庭用电。相反,我们发现可再生能源在BYOP中远不如燃气普遍:我们估计,对于当前的提案,到2032年,只有不到20%的能源将来自可再生能源。

But BYOP projects aren’t the only new fossil sources that are coming online to meet the skyrocketing energy demands of AI data centers. Another 200 GW of new fossil power plants is being built on the grid to meet growing demand, due in large part to data centers.1

但BYOP项目并不是为满足AI数据中心飙升的能源需求而上线的唯一新的化石燃料来源。另有200 GW的新化石燃料发电厂正在电网建设中,以满足不断增长的需求,这在很大程度上是由于数据中心造成的。1

As a case study of how the AI buildout is driving both new BYOP and grid fossil infrastructure, we analyzed the compute commitments of a single company: Anthropic.

作为AI建设如何推动新的BYOP和电网化石基础设施的案例研究,我们分析了一家公司的计算承诺:Anthropic。

Map of Anthropic’s data centers and associated power plants. See our full dataset for details of each site.

Anthropic的数据中心及相关电厂地图。详见我们的完整数据集以获取每个站点的详细信息。

Figure 1. Breakdown of power source for Anthropic’s compute.

图1. Anthropic计算电源来源细分。

Finding 1: Anthropic has made no direct commitments to renewable energy in the U.S. Though Anthropic has stated “We’re also working to broaden our energy mix with geothermal, wind, solar, and emerging technologies”, its only publicly disclosed commitments, contract, or investments in renewable power are in Norway and Canada (as of November 2026). In contrast, Anthropic is directly procuring fossil power equipment—it recently “bought commitments for 1.7 gigawatts of heavy-duty [gas] generators for $3.4bn”.

发现1:Anthropic在美国未做出任何对可再生能源的直接承诺。尽管Anthropic表示“我们也在努力通过地热、风能、太阳能和新兴技术扩大我们的能源组合”,但其唯一公开披露的可再生能源承诺、合同或投资都在挪威和加拿大(截至2026年11月)。相比之下,Anthropic正在直接采购化石燃料设备——它最近“购买了1.7吉瓦的重型[燃气]发电机承诺,价值34亿美元”。

Finding 2: Anthropic’s currently contracted data centers in the U.S. will be overwhelmingly powered by fossil fuels in the near term. By considering on-site gas and the grid power plants which are likely to meet Anthropic’s added load (i.e. marginal generators), we estimate about 87% of the company’s power will come from gas and 11% from coal in 2028. As of October 2026, Anthropic has contracted 15 GW of compute; of this, about 5.9–9.6 GW is contracted to specific data center sites. For a sense of scale, 9.6 GW could power about 7 million homes or cover 18% of the peak power demand of California—the world’s 4th largest economy.

发现2:Anthropic目前在美国签约的数据中心在短期内将主要由化石燃料供电。通过考虑现场燃气以及可能满足Anthropic新增负荷的电网电厂(即边际发电机),我们估计到2028年,该公司约87%的电力将来自天然气,11%来自煤炭。截至2026年10月,Anthropic已签约15 GW的计算能力;其中,约5.9–9.6 GW已签约给特定的数据中心站点。为了了解规模,9.6 GW可以为约700万户家庭供电,或覆盖加州峰值电力需求的18%——加州是世界第四大经济体。

This demand will be met with a mix of new on-site gas, new grid gas, and existing grid gas, coal, and nuclear. In the short term, no grid renewables are attributed to Anthropic’s power use, because—without commitments to new renewable capacity—new load on the grid will be met by dispatchable, marginal fossil resources.2 For more details, see our full dataset and our methodology below.

这一需求将通过新增现场制气、新增电网用气以及现有的电网用气、煤炭和核能来满足。短期内,Anthropic 的电力消耗未计入任何电网可再生能源,因为——在没有对新增可再生能源容量做出承诺的情况下——电网新增负荷将由可调度的边际化石资源满足。2 更多详情,请参阅我们的完整数据集及下文的方法论。

Figure 2. Anthropic’s emissions from power consumption expected in 2028. Emissions for Google, Microsoft, and Meta are annual Scope 2, location-based emissions from their most recent sustainability reports. California power sector emissions are for all power plants operating within the state (source: EIA).

图 2. Anthropic 预计 2028 年因电力消耗产生的排放量。Google、Microsoft 和 Meta 的排放数据为其最新可持续发展报告中的年度范围二(Scope 2)基于位置的排放量。加州电力部门排放量涵盖在该州运营的所有发电厂(来源:EIA)。

Finding 3: Total CO2 emissions from Anthropic’s power use at these sites could reach 17–38 million MtCO2e per year in 2028, when this capacity is expected to be online. This range reflects uncertainty in Anthropic’s average power use, due to factors such as cooling needs and average utilization (see methodology below). In our mid-case, Anthropic will emit 32 million MtCO2e in 2028. These totals will continue to grow—possibly doubling by 2030, as some analysts expect Anthropic to secure 30 GW by 2030.

发现 3:到 2028 年这些设施预计投入运行时,Anthropic 在这些站点的电力使用所产生的二氧化碳总排放量可能达到每年 1700 万至 3800 万吨 CO2e。这一范围反映了 Anthropic 平均电力消耗的不确定性,原因包括冷却需求和平均利用率等因素(见下文方法论)。在我们的基准情景中,Anthropic 在 2028 年的排放量将为 3200 万吨 CO2e。这些总量将继续增长——正如一些分析师所预期的那样,Anthropic 可能在 2030 年前获得 30 GW 的容量,届时排放量可能翻倍。

To put these figures in context, Anthropic’s CO2 emissions from power use in 2028:

为了将这些数据置于背景中,Anthropic 2028 年因电力使用产生的二氧化碳排放量:

  • could exceed the emissions of all of California’s power generation (31.1 MMtCO2e in 2024, not including imports).
  • could exceed Meta, Microsoft, and Google’s combined Scope 2 emissions from 2025 (their location-based emissions, before renewable energy offsets, were 5.9 million, 12 million and 15 million MtCO2e, respectively)3
  • would represent a 16–36% increase over 2024 levels of the entire U.S. data center sector (105 MMtCO2e).
  • would increase the entire U.S.’s power sector emissions (1,485 MMtCO2e in 2025) by 1.1–2.5%.
  • 可能超过加州所有发电量的排放量(2024 年为 3110 万吨 CO2e,不含进口电力)。
  • 可能超过 Meta、Microsoft 和 Google 2025 年范围二(Scope 2)排放量的总和(它们基于位置的排放量,在可再生能源抵消之前,分别为 590 万吨、1200 万吨和 1500 万吨 CO2e)3
  • 将占整个美国数据中心行业 2024 年排放水平(1.05 亿吨 CO2e)的 16%–36%。
  • 将使整个美国的电力部门排放量(2025 年为 14.85 亿吨 CO2e)增加 1.1%–2.5%。

Finding 4: Anthropic’s data centers are sited in areas where the grid mainly uses coal and gas. We estimate the average carbon intensity of Anthropic’s power to be 1,033–1,076 lb CO2e/MWh, 35% higher than the U.S. grid average (767 lb CO2e/MWh).4

发现 4:Anthropic 的数据中心选址于电网主要使用煤炭和天然气的地区。我们估计 Anthropic 电力的平均碳强度为 1033–1076 磅 CO2e/MWh,比美国电网平均水平(767 磅 CO2e/MWh)高出 35%。4

Figure 3. CO2e and NOx emissions factors for on-site and grid power serving each of Anthropic’s data center sites.

图 3. 服务于 Anthropic 各数据中心站点的现场电力和电网电力的 CO2e 和 NOx 排放因子。

Finding 5: 80% of on-site power uses inefficient simple cycle turbines and engines. About 25% (2.5 GW) of Anthropic’s contracted power will come from on-site, behind-the-meter gas. 80% of this on-site capacity consists of inefficient simple cycle turbines and engines, which emit more pollution per unit of electricity than modern combined cycle plants (see our report for more details on the types of power generation being used for on-site gas).

发现5:80%的现场电力使用低效的简单循环燃气轮机和发动机。Anthropic签约电力的约25%(2.5 GW)将来自现场、电表后的天然气发电。这80%的现场容量由低效的简单循环燃气轮机和发动机组成,其单位发电量的污染排放量高于现代联合循环发电厂(详见我们的报告,了解用于现场天然气的各类发电方式的更多细节)。

Finding 6: Based on EPA’s nationally-averaged benefit-per-ton estimates, air pollution from Anthropic’s on-site and grid power use could cause $2–3 billion in annual health damages, with total emissions of over 13,000 tons per year (tpy) of nitrogen oxides (NOx) and 2,000 tpy of fine particulate matter (PM2.5).

发现6:根据美国环保署(EPA)全国平均的单位吨效益估算,Anthropic现场和电网用电产生的空气污染可能导致每年20亿至30亿美元的健康损害,年总排放量为超过13,000吨氮氧化物(NOx)和2,000吨细颗粒物(PM2.5)。

In October 2026, Anthropic outlined its “approach to responsible data center development”, stating: “We follow the air permitting process everywhere we operate and require the same of the plants powering our data centers. Those plants must also use emissions control technology, including selective catalytic reduction [SCR].” However, Anthropic has used compute capacity at SpaceX’s Colossus 2 facility since May 2026, which still receives most of its power from temporary, unpermitted turbines, the majority of which are not equipped with SCR. Anthropic will use as much as 600 MW of power from Colossus 2 by the end of 2026 (see methodology below).

2026年10月,Anthropic概述了其“负责任的数据中心开发方法”,声明称:“我们在所有运营地区都遵循空气许可流程,并要求为数据中心供电的电厂同样遵守。这些电厂还必须使用排放控制技术,包括选择性催化还原[SCR]。”然而,自2026年5月以来,Anthropic一直在使用SpaceX的Colossus 2设施的算力,该设施的大部分电力仍来自临时、未获许可的涡轮机,其中大多数未配备SCR。到2026年底,Anthropic将使用高达600 MW来自Colossus 2的电力(见下文方法论)。

Anthropic has also contracted 460 MW (and is in talks for up to 920 MW) of power from Nscale’s Monarch Compute Campus in Mason, West Virginia. This facility will be powered by inefficient reciprocating engines which have significant formaldehyde and hazardous air pollutant (HAP) emissions compared to conventional gas power plants.

Anthropic还与Nscale公司签订了从西弗吉尼亚州梅森市的Monarch Compute Campus获取460 MW电力(并正在洽谈最高920 MW)的合同。该设施将由低效的往复式发动机供电,与常规燃气发电厂相比,这些发动机会产生大量的甲醛和有害空气污染物(HAP)。

For more, see our full dataset on Anthropic’s compute and our report on BYOP.

更多信息,请参阅我们关于Anthropic算力的完整数据集以及关于BYOP的报告。

Methodology

方法论

We gathered details about Anthropic’s data center commitments from Epoch AI’s tracker, Anthropic’s announcements and filings, announcements and filings from partners (including Amazon and SpaceX), and reporting from The Information, Semafor, and others.

我们从Epoch AI的追踪器、Anthropic的公告和文件、合作伙伴(包括亚马逊和SpaceX)的公告和文件,以及The Information、Semafor等媒体的报道中收集了关于Anthropic数据中心承诺的详细信息。

We first identified the source for each data center’s power. For projects with on-site gas (Monarch, Nexus, Colossus 2) or new grid gas (including indirectly contracted projects such as the Schahfer expansion for the AWS New Carlisle site and Entergy Mississippi’s gas plants for AWS’s Madison and Ridgeland facilities) we used emissions factors from permits where available, or permit values from comparable facilities. For grid-connected facilities without associated new generation capacity, we assume these sites will be powered by marginal, dispatchable grid capacity. We used EPA’s AVERT tool to model which power plants would meet the new incremental load from Anthropic’s facilities based on each site’s expected power use and region. AVERT uses historical EPA data for these power plants to model the expected short-run marginal emissions rate of CO2 and criteria pollutants (NOx, PM2.5, etc.). We use AVERT because we are interested in the short-term impacts from new data centers coming online in the next several years.

我们首先确定了每个数据中心电源的来源。对于拥有现场燃气(Monarch、Nexus、Colossus 2)或新增电网燃气(包括间接签约项目,如 AWS New Carlisle 场地的 Schahfer 扩建项目,以及 Entergy Mississippi 为 AWS 的 Madison 和 Ridgeland 设施提供的燃气电厂)的项目,我们在可用时使用了许可证中的排放因子,或在不可用时使用了可比设施的许可证数值。对于没有关联新增发电容量的并网设施,我们假设这些站点将由边际可调度电网容量供电。我们使用美国环保署(EPA)的 AVERT 工具,根据各站点的预期电力使用和所在区域,模拟哪些发电厂将满足 Anthropic 设施带来的新增增量负荷。AVERT 利用 EPA 的历史数据对这些发电厂进行建模,以预测二氧化碳及常规污染物(NOx、PM2.5 等)的预期短期边际排放率。我们使用 AVERT 是因为我们关注的是未来几年内新数据中心上线所带来的短期影响。